IP Master UPS

Check the new version
IP Master Plus

Specifications

Views

Products

POOIP0303 - IP Master 20 KVA TT

  • Type I : Online Double Conversion
  • Type II : TT
  • Type III : Low Frequency
  • Puissance : 18000 W
  • Voltage : 20000 VA
  • Power Factor : 0,8
  • Transfer Time : 0
  • By-pass : Automatic/ Manual/ Maintenance
  • Backup Autonomy : 15-20 mins at full load minutes
  • Number of Batteries : 32
  • Battery types : 12 V 9 Ah
  • Interface : Automatic shutdown software inclusive
  • warranty : Three years effective from date of commissioning
1 pcs / carton
413.00 kg
1.14 cbm

POOIP0307 - IP Master 40 KVA TT

  • Type 1(Low frequency technology True Online Double Conversion Uninterruptible Power Supply) : Low Frequency technology UPS
  • Type 2(In and OUT) : T/T
  • Type 3(Power) : 36000 W
  • Type 4(Voltage) : 40 KVA
  • Type 5(Power Factor) : 0,9
  • Type 6(Transfer time) : 0 ms
  • Type 7(Backup autonomy) : 15-20 min at full load mn
  • Type 8(By-pass) : Auto/ Manual/ Maintenance
  • Type 9(Interface) : Network communication interface: Rs232/ 485/ USB/
  • Type 10(Frequency type) : Low Frequency
  • Type 11(Protection) : Built-in Galvanic Isolating Transformer
  • Type 12(Frequency) : 50/ 60 Hz
  • Type 13(Input Frequency Range) : 45 ~ 65 Hz
  • Type 14(Maximum rate of change for frequeency) : 0.1 Hz/s
  • Type 15(Input frequency tolerance) : ±10 %
  • Type 16(Maximum change rate of sync frequency) : 1 Hz/s
  • Type 17(Output frequency range) : 45 ~ 65 (±0.05%) Hz
  • Type 18(Voltage stability transient state test) : ±5 %
  • Type 19(IEC62040-3 (5.3.1), including 0-100-0% load transient. Transient recovery time is 20ms, with an accuracy of 1) : Recovery time %
  • Type 20(Greater efficiency (energy) yield up to 95 at full load) : Efficiency %
  • Type 21(Crest factor) : 3:1
  • Type 22(Noise level) : <60dB at 1m
  • Type 23(Rectifier Indicator/ Bypass Indicator/ Battery Indicator/ Inverter Indicator/ Output & Input Indicator/ Alarm status indicator/) : Indicators
  • Type 24(Bypass over-protection/ UPS feed protection/ maintenance bypass interlock protection/ 1. Input current and short circuit protection/ 3. Ground fault protection/) : Protection
  • Type 25(serial port RS232-1, RS232-2, RS 485, and Instellislot (Intellislot 1, Intellislot 2, Intellislot 3) used for installing SNMP card, UPS JBUS/MODBUS adapter card and dry contact card.) : Communication port
  • Type 29(I/O voltage, Power, frequency, power factor, battery voltage, current, battery status, load percentage, UPS status, history record..) : LCD display
  • Type 30(< 2% linear mode and < 3% non-linear mode) : Total Harmonic Distortion (THD)
1 pcs / carton
409.00 kg
0.80 cbm

POOIP0311 - IP Master 80 KVA TT

  • Type 1 : Online Double Conversion
  • Type II : T/T
  • Power in W : 72000 W
  • Capacity : 80 KVA
  • Power Factor : 0.9
  • Transfer time : 0 ms
  • Backup autonomy at full load : 15-20 min
  • By-pass : Auto/Manual
  • Num of batteries (Standard config) : 32
  • Battery type : 12 V 38 AH
  • Shutdown interface : Inclusive
  • Type of frequency : Low Frequency
  • Warranty : Three (3) years from date of commissioning

Specifications